180 9424200994 Rev N
Figure 120. Setting Group Setup Screen
Table 71. Operational Settings
Setting
Range
Purpose
Default
Mode
Disabled
Discrete Inputs
Binary Inputs
Sets the mode of the setting group selection function.
(If Auto mode is desired, logic mode must be either 1 or
2.)
Disabled
Source*
CT Circuit 1 or CT
Circuit 2
n/a
n/a
Switch
Threshold
0 to 25A (5A CTs)
0 to 5A (1A CTs)
Measured current of the SG0 Monitor Setting that must
be exceeded for a setting group change to occur. (Set in
increments of 0.01A)
0
Switch
Time
0 = Disabled
1 to 60 minutes
Time, in minutes, that determines when a setting change
occurs once the Switch Threshold setting is exceeded.
0
Return
Threshold
0 to 25A (5A CTs)
0 to 5A (1A CTs)
Measured current of the SG0 Monitor Setting that the
monitored current must decrease below in order for a
return to SG0. (Set in increments of 0.01A)
0
Return
Time
0 = Disabled
1 to 60 minutes
Time, in minutes, that determines when a return to SG0
will occur once the monitored current has decreased
below the Return Threshold setting.
0
Setting Groups BE1-11g