9424200994 Rev N 179
Figure 119. Setting Group Logic Block
Table 70. Logic Inputs and Outputs
Name
Logic
Function
Purpose
Automatic Input
True when automatic control is enabled and false when logic
control is enabled
D0, D1, D2, D3
Inputs
Meaning depends upon the Mode setting
SG0, SG1, SG2, SG3
Outputs
True for the active setting group
SGCACTIVE
Output
True when Setting Group Control is Active
SGCLOVRD
Output
True when Setting Group Control is overridden by logic
Operational Settings
Setting group operational settings are configured on the Setting Group Setup screen (Figure 120) in
BESTCOMSPlus. Setting ranges and defaults are summarized in Table 71.
BE1-11g Setting Groups