3-20 BE1-851 Modbus™ Protocol 9289900992 Rev F
47389-92 Current Active Logic Scheme ASC(8)
Read Only:
Current active logic name.
47393 Reclose Status
Read only:
0 for Off
1 for Timing reclose #1
2 for Timing reclose #2
3 for Timing reclose #3
4 for Timing reclose #4
5 for Wait
6 for Lockout
7 for Reset
8 for Timing fail
9 for Timing reset
47394-95 Breaker Contact Duty Log - Phase A FP
47396-97 Breaker Contact Duty Log - Phase B FP
47398-99 Breaker Contact Duty Log - Phase C FP
Read:
If Breaker Duty Type = Off or Maximum Breaker Duty = 0, reads undefined
floating point value of 0xFFFFFFFF. Otherwise, reads 0.00 to 200.00%.
Write:
0 to 200%
47400-01 Breaker Operations Counter LI
Read and Write:
0 to 99,999
47410-11 Yesterday's Peak Demand Current - Phase A FP
47415-16 Yesterday's Peak Demand Current - Phase B FP
47420-21 Yesterday's Peak Demand Current - Phase C FP
47425-26 Yesterday's Peak Demand Current - Neutral FP
47430-31 Yesterday's Peak Demand Current - Neg-Seq FP
Read only:
Any value (amps)
47412 Yesterday's Peak Demand Timestamp - Day INT
47417 Yesterday's Peak Demand Timestamp - Day INT
47422 Yesterday's Peak Demand Timestamp - Day INT
47427 Yesterday's Peak Demand Timestamp - Day INT
47432 Yesterday's Peak Demand Timestamp - Day INT
Read only:
Any value (days since 01/01/1984).
47413-14 Yesterday's Peak Demand Timestamp - Millisecond LI
47418-19 Yesterday's Peak Demand Timestamp - Millisecond LI
47423-24 Yesterday's Peak Demand Timestamp - Millisecond LI
47428-29 Yesterday's Peak Demand Timestamp - Millisecond LI
47433-34 Yesterday's Peak Demand Timestamp - Millisecond LI
Read only:
0 to 86,399,999 milliseconds.
47435-36 Today's Peak Demand Current - Phase A FP
47440-41 Today's Peak Demand Current - Phase B FP
47445-46 Today's Peak Demand Current - Phase C FP
47450-51 Today's Peak Demand Current - Neutral FP
47455-56 Today's Peak Demand Current - Neg-Seq FP
Read only:
Any value (amps)